All applications suitable for systems with LED lights!
The premises
This example shows a sports hall with daylight ingress through a
number of windows. The hall has two entrances and can be divided using a
curtain-type folding partition. An active IR reflection detector
detects the position of the partition. It is used for various types of
activity ranging from exercise gymnastics to indoor bandy and handball
matches. The various activities do not require equally strong lighting.
You can thus select between two individual lighting levels in each half
when the folding partition is closed, e.g.:
approx. 30 per cent - basic lighting/exercise lighting (automatic activation)
approx. 80 per cent - game lighting
The required lighting levels are set in the NV-2.
Light sources
The fittings in the hall have dimmable HF operating devices. We
recommend that the number of fittings be overdimensioned so that match
lighting can be adjusted to 80 per cent. There are several advantages to
this solution:
- The operating devices undergo a lower working temperature, thus considerably prolonging their life span.
- Increased life span for the fluorescent tubes.
- Reduced maintenance costs as a result of longer life span.
The control system is based on the EX-13 logic module and two NV-2
level selectors. Presence in the hall is detected by two PD-2200 IR
detectors with lens No. 15.
Folding partition closed:
When someone enters one half of the hall the basic lighting (30 per cent) is
automatically activated by the IR detector in this half if the natural
light from the windows is insufficient. It is controlled by a light
sensor that measures the light in the hall and blocks activation if the
light suffices. If the automatic activation is blocked the basic light
can be switched on individually for each half of the hall using the
spring-back on/off push-buttons.
If the activity in the hall requires more light the game lighting
can be switched on individually for each half of the hall using a
pulse-emitting high/low push-button. Renewed pressure on the button
switches the lighting down to basic light level.
When the presence ceases the lighting is switched off completely
following the delay (5 - 7 minutes) set in the IR detector in the empty
half of the hall. Manual deactivation is also possible using the on/off
push-buttons.
Folding partition open:
Because the folding partition has a curtain
construction it is flexible, and an active IR reflection detector is
therefore used to detect when the partition is open. The IR detector has
a higher tolerance for movement of the partition and must be used with
curtain-type partitions. Both the supplied reflector strips should be
used with the active IR detector and should be positioned to give the
most reliable detection. A magnetic switch can be used on rigid folding
partitions; see application 5B. Lighting control in each half of the
hall is combined when the partition is open. Base lighting is switched
on in the entire hall when presence is detected, and the IR detectors
work together. Match lighting can be switched on in the entire hall
using any “High-Low” push-button.
Positioning of detectors
Positioning of the detectors is crucial to function! The example shows how the detector should be positioned. With this positioning optimum detection is achieved upon entry. Furthermore, the detector does not see out through the entrance, which means the lighting is not switched on when someone passes by outside. When the folding partition is open the detectors in the middle of the hall interact, thus creating more reliable detection. The detectors are positioned in the corners furthest away from the entrances at a height of 2 - 2.5 m. The mounting height is very important for reliable detection. Mounting too high up can create relatively big areas with poor detection.
A protective grating is used for corner mounting to protect the detector against balls etc.
Positioning of the detectors is crucial to function! The example shows how the detector should be positioned. With this positioning optimum detection is achieved upon entry. Furthermore, the detector does not see out through the entrance, which means the lighting is not switched on when someone passes by outside. When the folding partition is open the detectors in the middle of the hall interact, thus creating more reliable detection. The detectors are positioned in the corners furthest away from the entrances at a height of 2 - 2.5 m. The mounting height is very important for reliable detection. Mounting too high up can create relatively big areas with poor detection.
Product IR detector PD-2200 2 ea. Logic module EX-13 Level selector NV-2 2 ea. Rectifier EXE-2000 Light sensor LS-10 Active reflection detector |
Order No. 13140 13164 13168 18108 13100 13478 |
Options Protective grating Dimmer Magnetic contact |
13039 13172 14527 |
Information for current budget | |
Product | Maximum current consumption (mA) |
IR detector PD-2200 | 25 |
Logic module EX-13 | 250 |